1-5 Field Setting / Function Setting for Indoor unit
Setting Mode
ITEM
CODE No. Setting Function
Default
Indoor unit field setting
Address
setting by
remote controller
01 Indoor unit address 00~63 00~63 00
02 Refrigerant circuit address 00~99 00~99 00
Filter 11 Filter indicator Interval 00 Default
01
Longer
02 Shorter
13 Filter sign display 00 Enable
01 Disable
02 Display only on central remote control
Airflow 20 Ceiling airflow 00 Default
(Cassette type only) 01 High ceiling
23 Vertical airflow direction 00 Default
01 Raise
24 Horizontal swing airflow direction 00 Default
01 Left half
02 Right half
Correction
30
Cool air temperature trigger
00 Default (0
°C
)
01 Temperature overshoot setting (+2
°C)
02 Temperature undershoot setting (-2
°C)
31 Heat air temperature trigger 00 Default (0
°C
)
01 Temperature undershoot setting (-6
°C)
02 Temperature slightly undershoot setting (-4
°C)
03 Temperature overshoot setting (+4
°C)
Change of 40 Auto restart 00 Enable
01 Disable
43 Cool air prevention 00 Enable
01 Disable (Ventilation mode)
46 External control 00 Start / Stop
01 Emergency stop
47 Error report target 00 All
01 Display only for central remote control
ITEM
CODE No.
Function 1
Classification
26
32
Model name Range of static pressure
ARXD07L ATH
0 to 90 Pa
ARXD09 L ATH
ARXD12L ATH
ARXD14L ATH
ARXD18 LATH
ARXD24L ATH 0 to 50 Pa
00
01
02
03
04
05
06
07
08
09
31
0 Pa
10 Pa
20 Pa
30 Pa
40 Pa
50 Pa
60 Pa
70 Pa
80 Pa
90 Pa
25 Pa
Static Pressure setting
- Slim Duct Only -
The Range of static pressure is
different from one model to other.
Temperature correction in Auto
00
01
Disable
Enable (Nonfunctional on J2 Series)