LED101
Inverter Compressor Operation Indication
Low Noise Mode
System stopped with compressor Temperature
Protection
System stopped with Low Pressure
Protection
System stopped with High Pressure
Protection
System stooped with Discharge Temp.
Protection
Defrost Operation
Oil Recovery Operation
Heating Mode
Cooling Mode
Idling(stop)
Indication type 7 Segment LED Pattern
4-1-2 OUTDOOR UNIT DISPLAY
LED104
LED105
POWER
MODE
ERROR
(GREEN)
LED102
(RED)
Blank
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" ROTECT "1"
"P" ROTECT "2"
"P" ROTECT "3"
"P" eak "C" ut
"L" OW "N" OISE
Blinking
Description
POWER
LED101
ERROR
LED102
ON
ON
OFF
OFF
"P" ROTECT "4"
ON
OFF
1 sec 1 sec
Peak Cut Mode
<Starting condition>
Discharge temp fixed value: 115°C
<Release condition>
3 minutes have elapsed and discharge temperature 80°C
<Starting condition>
Compressor temp fixed value :110°C
<Release condition>
3 minutes have elapsed and discharge temperature 80°C
<Starting condition>
Low pressure 0.05MPa
or low pressure 0.10MPa continues for 10 minutes
<Release condition>
3 minutes have elapsed and low pressure 0.17MPa
<Starting condition>
High pressure 4.00MPa
<Release condition>
5 minutes have elapsed and high pressure 3.50MPa
Refer to 02-10 page for operation.
Refer to 02-11 page for operation.
Refer to 02-08 page for operation.
04-02