2-3-2 Heating Operation
Fan step
11
10
9
8
7
6
5
4
3
2
1
0
800
700
660
660
670
590
540
540
450
410
340
340
270
250
0
0
0
0
0
0
0
0
0
0
AJ A36LALH AJ A45LALH AJ A54LALH
Fan speed (rpm)
Switching conditions of step
Fan step
11
8
5
5
Outside air temperature
sensor detected value
TAOUT 10°C
10°C TAOUT 15°C
15°C TAOUT 20°C
20°C TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
(Condition which lowers the fan speed)
High-pressure 3.30MPa and heat sink temperature 80°C
(Condition which raises the fan speed)
High-pressure saturation 3.20MPa or heat sink temperature 85°C
The initial speed of the first boot outdoor unit is detected by outdoor air temperature sensor value (TAOUT).
800
700
660
660
670
590
540
540
450
410
340
340
270
250
0
0
0
0
0
0
0
0
0
0
800
700
700
700
670
590
540
540
450
410
340
340
270
250
0
0
0
0
0
0
0
0
0
0