Check Point : ARXA24/ 30LATH (Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Lead wire
47.1 8%
27.4 8%
8.00 8%
8.00 8%
8.00 8%
Resistance value
(AC)
Thermal protector
Pr
VIOLET (Low)
BLUE (S-Lo)
PINK (Med)
RED (Hi)
BLACK
WHITE
150°C
at 20°C
Check Point : ARXA36/ 45LATH (Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Lead wire
20.1 8%
13.8 8%
6.50 8%
6.50 8%
6.50 8%
Resistance value
(AC)
Thermal protector
Pr
VIOLET (Low)
BLUE (S-Lo)
PINK (Med)
RED (Hi)
BLACK
WHITE
150°C
at 20°C