Check Point : ARXB14LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Lead wire
136.5 8%
125.6 8%
49.4 8%
23.7 8%
23.7 8%
Resistance value
(AC)
Thermal protector
Pr
VIOLET (Low)
BLUE (S-Lo)
PINK (Med)
RED (Hi)
BLACK
WHITE
140°C
at 20°C
Check Point : ARXB18LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Lead wire
89.7 8%
150 8%
197 8%
37.4 8%
37.4 8%
Resistance value
(AC)
Thermal protector
Pr
VIOLET (Low)
BLUE (S-Lo)
PINK (Med)
RED (Hi)
BLACK
WHITE
150°C
at 20°C
04-100