06-11
Procedure for compressor installation.
Reverse procedure to removing the compressor.
Precautions for installation of Compressor.
(1) When brazing, do not apply the flame to the terminal.
(2) When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.
Thermistor (Discharge)
Terminal Cover
Compressor wire
Thermistor (Comp.temp.)
Hook
HEATER (CRANK CASE)
Discharge side
Cut the binder, and
remove the heat insulation.
Remove the Thermistor(Discharge).
Remove the Thermistor(Comp.temp.)
and Thermistor(Discharge).
Remove the Terminal Cover and Compressor wire.
Loose the HEATER (CRANK CASE)
Remove the COMP BOLTs.
(3 places)
Heat up the brazed part of
the discharge side and disconnect.
Heat up the brazed part of the suction side and disconnect.
Remove the COMPRESSOR.
Suction side
BR Sheet
Caution
There is a possibility of catching fire to oil when removing by the welding.
Remove the BR Sheet before brazing.