EasyManua.ls Logo

Fujitsu AIRSTAGE V-II - Liquid Pipe Temp Sensor 2 Error

Fujitsu AIRSTAGE V-II
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquid Pipe Temp Sensor 2 Error
OK
DC
CN142
THERMISTOR
THERMISTOR
(SC.INT.GAS)
(SC.INT.LIQ)
THERMISTOR
(SC.EXT.GAS)
THERMISTOR
(SC.EXT.LIQ)
B
L
A
C
K
B
L
A
C
K
B
L
A
C
K
B
L
A
C
K
B
L
A
C
K
B
L
A
C
K
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BLA
CK
BLA
CK
Liquid pipe temperature thermistor 2
Liquid pipe temperature thermistor 2 short or open detected
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 22".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN142:3-4) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Liquid pipe temperature sensor 2 (CN142:3-4)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 83. 2
Error Code : 83
If the voltage does not appear, replace Main PCB and set up orignal address.
(Refer to 06-03 page Main PCB removal.)
If the voltage does not appear, replace Main PCB and set up orignal address.
04-45
Trouble shooting 37
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :

Table of Contents

Other manuals for Fujitsu AIRSTAGE V-II

Related product manuals