LED101
Inverter Compressor Operation Indication
Low Noise Mode
Compressor Temperature Protection is stopped
Low Pressure Protection is stopped
High Pressure Protection is stopped
Discharge Temp. Protection is stopped
Defrost Operation
Oil Recovery Operation
Heating Mode
Cooling Mode
Idling(stop)
Indication type 7 Segment LED Pattern
4-1-2 OUTDOOR UNIT DISPLAY
LED104
LED105
POWER
MODE
ERROR
(GREEN)
LED102
(RED)
Blank
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" ROTECT "1"
"P" ROTECT "2"
"P" ROTECT "3"
"P" eak "C" ut
"L" OW "N" OISE
"SN" OW
Blinking
Blinking
Description
POWER
LED101
ERROR
LED102
ON
ON
OFF
OFF
Snow Falling Protection Fan mode
"P" ROTECT "4"
Constant Speed Compressor Operation Indication
Inverter Compressor and
Constant Speed Compressor Operation Indication
Blinking
0.5 sec
ON
OFF
ON
OFF
ON
OFF
1 sec 1 sec
0.24 sec
0.5 sec
0.24 sec
Peak Cut Mode
<Starting condition>
Discharge temp fixed value (INV:110°C, constant speed:115°C)
<Release condition>
3 minutes have elapsed and discharge temperature 80°C
<Starting condition>
Compressor temp fixed value (INV:112°C, Constant speed:120°C)
<Release condition>
3 minutes have elapsed and discharge temperature 80°C
<Starting condition>
Low pressure 0.05MPa
or low pressure 0.10MPa continues for 10 mins
<Release condition>
3 minutes have elapsed and low pressure 0.17MPa
<Starting condition>
High pressure 4.00MPa
<Release condition>
5 minutes have elapsed and high pressure 3.50MPa
Refer to 02-10 page for operation.
Refer to 02-11 page for operation.
Refer to 02-09 page for operation.
Refer to 02-08 page for operation.