EasyManua.ls Logo

Fujitsu AIRSTAGE V-II - Auto Address Setting Error; Signal Amplifier Auto Address Error

Fujitsu AIRSTAGE V-II
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OK
OK
OK
1. Indoor unit power supply defective 2 Indoor unit overconnected
3.Communication line incorrect connection 4. Noise, momentary open
Outdoor unit Main PCB
Check Point 1 : Check the indoor unit power supply
Check the indoor unit power supply
Check Point 2 : Check the indoor unit number connection
Check if more than 64 indoor units are connected in a refrigerant circuit
Is it uncoupled or cut halfway ?
Connecting terminal position is correct as the installation manual shows ?
Check Point 4 : Check noise, momentary open, voltage drop
Check if power supply temporarily stops by outages or if strong noise is generated from
surrounding environment during auto address
Check Point 3 : Check the communication line connection
Indoor Unit : No Display
Outdoor Unit : E. 28. 1
Error Code : 28
04-69(01)
Auto Address Setting Error
When none of the connected indoor units answers during auto address
And when abnormal answer signal is input.
Trouble shooting 61
Indicate or Display:
Detective Actuators:
Detective details:
UTDOOR UNIT Error Method:
Forecast of Cause :
OK
OK
OK
1. Signal amplifier power supply defective 2. Signal amplifier overconnected
3. Signal amplifier auto address wrong setting 4. Noise, momentary open.
Outdoor unit Main PCB
Check Point 1 : Check signal amplifier unit power supply
Check signal amplifier unit power supply
Check Point 2 : Check the signal amplifier number connection
Check if more than 8 signal amplifiers are connected in a network
Check if signal amplifier auto address is set at the same time from multiple
outdoor units (master unit)
Check Point 4 : Check noise, momentary open, voltage drop
Check if power supply temporarily stops by outages or if strong noise is generated from
surrounding environment during signal amplifier auto address
Check Point 3 : Check the operation of signal amplifier auto address setting
Indoor Unit : No Display
Outdoor Unit : E. 28. 4
Error Code : 28
Signal Amplifier Auto Address Error
When abnormal answer signal is input during signal amplifier auto address
Trouble shooting 62
Indicate or Display:
Detective Actuators:
Detective details:
UTDOOR UNIT Error Method:
Forecast of Cause :
Check if communication line is correctly connected