SERVICE PARTS INFORMATION 10
Resistor, Cement
Check Point 1 : Appearance check
Check Point 2 : Electric check
Set the tester to the "Resistance" mode, and measure the resistance value between the terminals.
(No polarity)
Judge the result of as follows:
5.32 to 5.88 : Normal
Other than the above : Deteriorated, defective
No fissures, breaks, damage, etc. at the body and terminals section?
1. Surge prevention resistor (connected to magnetic contactor)
Set the tester to the "Resistance" mode, and measure the
resistance value between the terminals. (No polarity)
Judge the result of as follows:
31.35 to 34.65 : Normal
Other than the above : Deteriorated, defective
2. Balance resistor (connected to electrolytic capacitor)
SERVICE PARTS INFORMATION 11
Capacitor
Check Point 1 : Appearance check
Check Point 2 : Electric check
No short between terminals?
Explosion-proof not operated?
Electrolyte not leaking?
No abnormalities at threaded parts? (Stripped threads, deformation, damage, etc.)