02-07
2-3-2 Heating Operation
Fan step
16
15
14
13
12
11
10
9
8
7
880
860
830
700
600
500
420
360
320
300
880
860
830
700
600
500
420
360
320
300
880
860
830
700
600
500
420
360
320
300
920
870
820
700
600
500
420
360
320
300
920
870
820
700
600
500
420
360
320
300
AJ A72LALH AJ A90LALH AJ A108LALH AJ A126LALH AJ A144LALH
Fan speed (rpm)
Switching conditions of step
Fan step
16
12
7
7
Outside air temperature
sensor detected value
TAOUT 10°C
10°C TAOUT 15°C
15°C TAOUT 20°C
20°C TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
Other outdoor units are normally operated at fan step 16.
(Condition which lowers the fan speed)
High-pressure 3.30MPa and heat sink temperature 75°C
(Condition which raises the fan speed)
High-pressure saturation 3.20MPa or heat sink temperature 80°C
The initial speed of the first boot outdoor unit is detected by outdoor air temperature sensor value (TAOUT).
intermittent 6
intermittent 5
intermittent 4
intermittent 3
intermittent 2
intermittent 1
6
5
4
3
2
1
Intermittent fan mode
Fan speed 0 rpm
duration time T ( sec )
Fan step Fan mode
6
12
19
26
33
40
7
Fan speed 300 rpm
duration time ( sec )
When switched from normal fan step to intermittent fan step, always start from 300rpm/7sec.
When there was a change during intermittent step 1-6, switching is performed at the time the current speed
duration time reaches time-up.
7 sec 7 sec 7 sec
300 rpm
[ T ] sec [ T ] sec
0 rpm
Normal fan step
Intermitten fan step
Time
Fan speed