- 117 -
MULTI TYPE
4 rooms type
11. Safety devices
*: Printed Circuit Board
Indoor unit
type
Model name PCB* fuse
Fan motor thermal
protector
Terminal thermal
fuse
Float
switch
Compact
cassette
AUU7RLF
AUU9RLF
AUU12RLF
AUU18RLF
250 V, 3.15 A
Activate: 212 ± 27 °F
(100 ± 15 °C)
Fan motor stop
Reset: 203 ± 18 °F
(95 ± 10 °C)
Fan motor restart
―○
Slim duct
ARU7RLF
ARU9RLF
ARU12RLF
ARU18RLF
ARU24RLF
250 V, 3.15 A
Activate: 275 ± 27 °F
(135 ± 15 °C)
Fan motor stop
Reset: 239 ± 27 °F
(115 ± 15 °C)
Fan motor restart
―○
Wall mounted
ASU7RLF1
ASU9RLF1
ASU12RLF1
ASU15RLF1
250 V, 3.15 A
Activate: 221 ± 18 °F
(105 ± 10 °C)
Fan motor stop
Reset: 194 ± 18 °F
(90 ± 10 °C)
Fan motor restart
――
ASU18RLF
ASU24RLF
250 V, 3.15 A
Activate: 302 ± 27 °F
(150 ± 15 °C)
Fan motor stop
Reset: 248 ± 27 °F
(120 ± 15 °C)
Fan motor restart
Activate: 216 °F
(102 °C)
Floor
AGU9RLF
AGU12RLF
AGU15RLF
250 V, 3.15 A
Activate: 302 ± 27 °F
(150 ± 15 °C)
Fan motor stop
Reset: 248 ± 27 °F
(120 ± 15 °C)
Fan motor restart
Activate: 216 °F
(102 °C)

Table of Contents