- 231 -
OUTDOOR UNIT
AOU36RLXFZH
11. Electrical characteristics
*: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
MCA: Minimum Circuit Ampacity (Calculation based on UL1995)
CKT. BKR: Circuit Breaker
Model name AOU36RLXFZH
Power supply Voltage V 208/230 ~
Frequency Hz 60
MCA A 31.5
Starting current A 12.9
Wiring spec. * CKT. BKR A 40
Power cable AWG 8