- 125 -
MULTI TYPE
4 rooms type
Circuit diagram example
Relay spec.: Rated DC 12 V, 50 mA to less.
*: Make the distance from the PCB to the connected unit within 33 ft (10 m).
!
CAUTION
Locate an external heater between the indoor unit and the outlet.
Be sure to use delay control of a fan.
Optional part
Indoor unit type Parts name Model name
Compact cassette
Slim duct External control set UTD-ECS5A
Wall mounted
Floor
Locally purchased
Indoor unit
control PCB
Connector
1
12 V
On/Off
2
Signal
Relay
power
supply
Example: Heater
Connected unit
Example:
Relay unit
33 ft
(10 m)*
On
Off
Operation
Stop
Heating
operation
Indoor unit fan
On
Off
Output signal
1min
External
Heater
Supply air Return air
Indoor unit