- 190 -
OUTDOOR UNIT
AOU36RLXFZH
NOTE:
Specifications are based on the following conditions.
• Power source of specifications: 230 V
• 2 or more indoor units should be connected.
• Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit]
• The total ability of connected a indoor unit is up to 39,000 Btu from 27,000 Btu.
• Input in the table are calculated based on the maximum indoor unit input combinations.
27
-10.0 6.72 0.74 7.59 0.75 8.00 0.76 8.50 0.77 9.16 0.77 9.44 0.78
-5.0 6.72 0.77 7.59 0.79 8.00 0.79 8.50 0.80 9.16 0.81 9.44 0.81
0.0 6.72 0.81 7.59 0.82 8.00 0.83 8.50 0.84 9.16 0.84 9.44 0.85
5.0 6.72 0.90 7.59 0.91 8.00 0.92 8.50 0.93 9.16 0.94 9.44 0.95
10.0 6.72 0.99 7.59 1.01 8.00 1.01 8.50 1.03 9.16 1.04 9.44 1.04
15.0 6.72 1.36 7.59 1.39 8.00 1.40 8.50 1.41 9.16 1.43 9.44 1.44
20.0 6.72 1.73 7.59 1.76 8.00 1.78 8.50 1.80 9.16 1.82 9.44 1.83
25.0 6.72 1.91 7.59 1.94 8.00 1.96 8.50 1.98 9.16 2.00 9.44 2.02
30.0 6.72 2.09 7.59 2.12 8.00 2.14 8.50 2.16 9.16 2.19 9.44 2.20
35.0 6.72 2.23 7.59 2.27 8.00 2.29 8.50 2.31 9.16 2.34 9.44 2.35
40.0 6.35 2.43 7.18 2.47 7.57 2.49 8.10 2.52 8.67 2.55 8.93 2.56
46.1 6.35 2.63 7.18 2.68 7.57 2.70 8.10 2.73 8.67 2.76 8.93 2.78
Indoor unit
connecting
capacity
Outdoor
temperature
Indoor temperature
17.8 °CDB 21.1 °CDB 23.9 °CDB 26.7 °CDB 29.4 °CDB 32.2 °CDB
12.2 °CWB 15.6 °CWB 17.2 °CWB 19.4 °CWB 21.7 °CWB 22.8 °CWB
kBtu/h °CDB TC IP TC IP TC IP TC IP TC IP TC IP