- 207 -
OUTDOOR UNIT
AOU36RLXFZH
NOTE:
Specifications are based on the following conditions.
• Power source of specifications: 230 V
• 2 or more indoor units should be connected.
• Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit]
• The total ability of connected a indoor unit is up to 39,000 Btu from 27,000 Btu.
• Input in the table are calculated based on the maximum indoor unit input combinations.
28
-15 -17 18.1 2.62 17.7 2.68 17.2 2.73 16.8 2.78 16.4 2.84
-5 -7 20.5 2.76 20.0 2.82 19.5 2.88 19.1 2.94 18.6 3.00
5 3 29.7 3.85 29.0 3.93 28.3 4.01 27.6 4.09 26.9 4.17
14 12 31.6 3.80 30.8 3.88 30.0 3.96 29.3 4.04 28.5 4.12
23 19 33.4 3.61 32.6 3.68 31.8 3.76 31.0 3.84 30.2 3.91
32 28 34.3 3.47 33.5 3.54 32.7 3.61 31.9 3.68 31.0 3.75
41 37 34.3 2.99 33.5 3.05 32.7 3.11 31.9 3.17 31.0 3.23
47 43 34.3 2.43 33.5 2.49 32.7 2.54 31.9 2.59 31.0 2.64
50 47 34.3 2.43 33.5 2.48 32.7 2.53 31.9 2.58 31.0 2.63
59 50 34.3 2.41 33.5 2.46 32.7 2.51 31.9 2.56 31.0 2.61
68 59 34.3 2.31 33.5 2.36 32.7 2.41 31.9 2.46 31.0 2.50
75 65 34.3 2.23 33.5 2.28 32.7 2.33 31.9 2.37 31.0 2.42
27
-15 -17 17.4 2.51 17.0 2.56 16.6 2.61 16.2 2.67 15.8 2.72
-5 -7 19.8 2.65 19.3 2.70 18.8 2.76 18.4 2.81 17.9 2.87
5 3 28.7 3.69 28.0 3.77 27.3 3.84 26.6 3.92 25.9 4.00
14 12 30.4 3.64 29.7 3.72 29.0 3.79 28.3 3.87 27.5 3.95
23 19 32.2 3.46 31.4 3.54 30.6 3.61 29.9 3.68 29.1 3.75
32 28 33.1 3.32 32.3 3.39 31.5 3.46 30.7 3.53 29.9 3.60
41 37 33.1 2.86 32.3 2.92 31.5 2.98 30.7 3.04 29.9 3.10
47 43 33.1 2.34 32.3 2.39 31.5 2.44 30.7 2.48 29.9 2.53
50 47 33.1 2.33 32.3 2.38 31.5 2.43 30.7 2.48 29.9 2.53
59 50 33.1 2.31 32.3 2.36 31.5 2.41 30.7 2.46 29.9 2.51
68 59 33.1 2.22 32.3 2.27 31.5 2.31 30.7 2.36 29.9 2.40
75 65 33.1 2.14 32.3 2.19 31.5 2.23 30.7 2.28 29.9 2.32
Indoor unit
connecting
capacity
Outdoor temperature
Indoor temperature
60 °FDB 65 °FDB 70 °FDB 75 °FDB 78 °FDB
kBtu/h °FDB °FWB TC IP TC IP TC IP TC IP TC IP