EasyManua.ls Logo

Fujitsu AOU48RLXFZ - Transmission Line

Fujitsu AOU48RLXFZ
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. SYSTEM DESIGN
TRANSMISSION LINE4-3.
TRANSMISSION WIRING SPECIFICATIONS
Use Cable size Remarks
Between Outdoor unit to Branch box
Between Branch box to Branch box
Between Branch box to Indoor unit
14 AWG
208/230V 60Hz
3Wire + ground
Between Central remote controller to Branch box 22 AWG
Sheathed PVC cable
Polar 3core
TRANSMISSION WIRING LIMITATION
def
a
b
Central remote
controller
c
hig
l
jk
Branch box 3 (secondary)Branch box 2 (secondary)Branch box 1 (primary)
Maximum length [ft. (m)]
Outdoor unit - Branch box (primary) a 246 (75)
Branch box (primary) - Branch box (secondary)
(each unit)
b, c 246 (75)
Branch box - Indoor unit
(each unit)
d, e, f, g, h, i, j, k 246 (75)
Central remote controller - Branch box
(Total length)
l 1640 (500)
- (06 - 43) -