2. MODEL SELECTION
THE EXAMPLE OF CALCULATION3-2.
COOLING EXAMPLE3-2-1.
EXAMPLE 1
(When the connecting capacity for indoor unit is 100% or more)
Branch
box
Branch
box
Branch
box
Outdoor unit
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 Indoor unit 8
Room 1 Room 2 Room 3 Room 4 Room 5 Room 6 Room 7 Room 8
Main Piping length, L1=32.8ft. (10m) Branch Piping length, L1=32.8ft. (10m)
Design conditions
Design temperature
Indoor : 75°F DB / 63°F WB (23.9°C DB / 17.2°C WB)
Outdoor : 86°F DB (30°C DB)
Pipe length
Main piping length : L1=32.8ft. (10m)
Branch piping length : L2=32.8ft. (10m)
Operation mode: Cooling
Selection of indoor unit
Room 1 Room 2 Room 3 Room 4 Room 5 Room 6 Room 7 Room 8
Remark
A-1 Cooling heat load Btu 5800 5800 5800 5800 5800 5800 5800 5800
A-2 Indoor unit models
ASU7 ASU7 ASU7 ASU7 ASU7 ASU7 ASU7 ASU7
A-3 Rated capacity (TC
in
)
r
Btu 7000 7000 7000 7000 7000 7000 7000 7000
Cooling
A-4 Total rated capacity ∑(TC
in
)
r
Btu 7000 x 8 = 56000
Sum of A-3
A-5
Connecting indoor unit
capacity (Cp)
56000 / 48000 = 117% (80%≤Cp≤130%)
A-6
Capacity change rate by
suction temperature of
indoor unit
46.1 / 48.0 = 0.960
See Fig.1
A-7
Total capacity at design
temperature ∑(TC
in
)
d
Btu 56000 x 0.960 = 53760
(A-4) x (A-6)
Calculate the Maximum capacity of outdoor unit
Remark
B-1 Outdoor unit model AOU48RLXFZ
B-2 Rated capacity (TC
out
)
r
Btu 48000
Cooling
B-3 Capacity change rate by temperature conditions 47.4 / 48.0 = 0.988
See Fig.1
B-4 Capacity change rate by indoor units connecting capacity 52.4 / 48.0 = 1.092
See Fig.2
B-5 Compensation coefcient of pipe length 0.98 x 0.942 = 0.923
See 5-1.
B-6 Maximum capacity of outdoor unit (TC
out
)
c
Btu 48000 x 0.988 x 1.092 x 0.923 = 47800
(B-2) x (B-3) x (B-4) x (B-5)
Decide system capacity
Remark
C-1 System capacity Btu 47800
Smaller one of (A-7)
and (B-6)
Calculate actual capacity of each indoor unit
Room 1 Room 2 Room 3 Room 4 Room 5 Room 6 Room 7 Room 8
Remark
Actual capacity of each indoor
unit
Btu 5970 5970 5970 5970 5970 5970 5970 5970
(A-3) x (C-1) / (A-4)
Actual capacity of all indoor units is larger than cooling heat load of each room.
- (02 - 05) -