6. SYSTEM DESIGN
WIRING RULES
Example 1 (Not good)
Branch box (secondary)
Transmission line
Do not connect outdoor unit to secondary type branch box.
Always connect primary type branch box to outdoor unit.
Example 2 (Not good)
Branch box (primary) Branch box (primary)
Transmission line
Do not interconnect primary type branch boxes.
Only 1 primary type branch box can be connected in 1 multi system.
Example 3 (Not good)
Branch box (primary)
Transmission line
Do not interconnect indoor units.
Always connect branch box to indoor unit.
- (06 - 45) -
SYSTEM
DESIGN
SYSTEM
DESIGN