6. SYSTEM DESIGN
STOP OPERATION MODE
It is possible to switch to Batch stop or Emergency stop and Normal operation by using external
input.
Circuit diagram example
Contact capacity : 24VDC or more, 10mA or more.
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*33ft. (10m)
Connected unit
Ex.) Switch
* Make the distance from the PC board to the connected unit within 33ft. (10m).
Use the following parts and construct a circuit as shown above.
Set the "Batch stop" or "Emergency stop" pattern, refer to "5.FUNCTION SETTING"
When function setting is "Batch stop" mode
Remote controller
On On
Input signal
On
Off
Air conditioner
Operation
Stop
Command
Batch stop
Normal
Remote control
operation validity
- (06 - 93) -