6. SYSTEM DESIGN
COMPRESSOR STATUS OUTPUT
Compressor operation status signal is produced when the compressor is running.
Circuit diagram example
1) Power supply
Voltage (Chart sign=Vcc) : DC 24V or less
2) Load
Load : DC 500mA or less is recommended
Signal
Outdoor unit
control PC board
Connected unit
Connector
1
2
Field supply
*33ft. (10m)
Vcc
+
+
-
Load
Vcc
Power
supply
* Make the distance from the PC board to the connected unit within 33ft. (10m).
ON
OFF
Operation
Stop
Compressor
Output signal
status
Parts (Optional)
Parts name External connect kit
Model name UTY-XWZXZ3
- (06 - 96) -
SYSTEM
DESIGN
SYSTEM
DESIGN