6. SYSTEM DESIGN
EXTERNAL OUTPUT7-2-2.
OPER ATION STATUS OUTPUT
Compact Cassette Slim Duct
Comapct Wall
Mounted
Wall Mounted
Connector CN103 CN103 CN304 CN16
An air conditioner operation status signal can be output.
Circuit diagram example
Relay spec.:
Max.24V DC, 10mA to less
than 500mA.
Field supply
Ex.)Display
Indoor unit
control PC board *1
Connected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
33ft. (10m)
*2
24V DC
*1: PC board of Communication kit is used for Compact wall mounted type.
*2: Make the distance from the PC board to the connected unit within 33ft. (10m).
ON
OFF
Operation
Stop
Indoor unit
Output signal
Parts (Optional)
Compact Cassette Slim Duct Compact Wall Mounted Wall Mounted
Parts name External connect kit
Model name UTY-XWZX
Compact Cassette Slim Duct
Compact Wall
Mounted
Wall Mounted
Parts name - - Communication kit -
Model name - - UTY-XCBXZ1 -
* For operating the EXTERNAL OUTPUT function, the Compact wall mounted type requires the communication kit
(UTY-XCBXZ1) in addition to the wire (UTY-XWZX).
- (06 - 101) -
SYSTEM
DESIGN
SYSTEM
DESIGN