4. INDOOR UNITS
Note : Specifications are based on the following conditions.
Power source of specifications : 230V
Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB.
Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB.
Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit]
Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].
SPECIFICATIONS2.
COMPACT CASSETTE TYPE2-1.
Model name AUU9RLF AUU12RLF AUU18RLF
Power source 1ø 208/230V 60Hz
Available voltage range 187-264V
Capacity
Cooling Rated
Btu/h 9,000 12,000 18,000
kW 2.64 3.51 5.28
Heating Rated
Btu/h 10,200 13,500 20,000
kW 3.00 3.96 5.85
Moisture removal pints/h(l/h) 2.5 (1.2) 3.2 (1.5) 4.2 (2.0)
Power consumption W 18 23 39
Running current A 0.15 0.19 0.30
Fan
Airflow
rate
Cooling
High
CFM
(m
3
/h)
318 (540) 359 (610) 441 (750)
Med 288 (490) 312 (530) 359 (610)
Low 259 (440) 277 (470) 306 (520)
Quiet 230 (390) 241 (410) 241 (410)
Heating
High 318 (540) 359 (610) 471 (800)
Med 288 (490) 312 (530) 418 (710)
Low 259 (440) 277 (470) 353 (600)
Quiet 230 (390) 241 (410) 265 (450)
Fan Type × Q'ty Turbo × 1
Fan Motor Output W 42 42 42
Sound pressure level
Cooling
High
dB(A)
33 37 42
Med 31 33 37
Low 29 31 33
Quiet 27 28 29
Heating
High 34 37 44
Med 32 33 40
Low 29 31 37
Quiet 27 28 30
Heat
exchanger
Dimension (H×W×D) in. (mm)
8-9/32 × 51-9/16 × 17/32 + 8-9/32 × 49-7/32 × 17/32
(210×1310×13.3 + 210×1250×13.3)
Fin pitch FPI 21
Rows × Stages 2×10
Pipe type Copper tube
Fin Type Aluminium
Enclosure
Material PS
Color
White
(Approximate color of Mansell N9.25 /)
Dimensions
( H×W×D )
Net
Unit
in.(mm)
9-21/32 × 22-7/16 × 22-7/16 (245×570×570)
Panel 1-15/16 × 27-9/16 × 27-9/16 (49 × 700 × 700)
Gross
Unit 10-7/16 × 28-3/4 × 24-19/32 (265×730×625)
Panel 4-23/32 × 30-1/8 × 29-23/32 (120 × 765 × 755)
Weight
Net
Unit
lb. (kg)
33 (15)
Panel 5.7(2.6)
Gross
Unit 40 (18)
Panel 10(4.5)
Connection
pipe
Size
Liquid
in.(mm)
1/4 (6.35)
Gas 3/8 (9.52) 1/2 (12.7)
Method Flare
Drain pipe
Material HARD PVC
size in.
Outer Diameter : 1-1/16
Inner Diameter : 3/4
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 88 (16 to 31)
Remote controller type Wired [Wireless(option)]
- (04 - 05) -
INDOOR
UNITS
INDOOR
UNITS