OUTDOOR UNIT
AOYG12-54LB
6-4. Model: AOYG30LBTA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50
Indoor unit is higher
than outdoor unit *1
30 - - - - 0.908 0.894 0.876
20 - - - 0.935 0.923 0.909 0.891
10 - - 0.968 0.951 0.938 0.924 0.906
7.5 - 0.982 0.972 0.954 0.942 0.928 0.909
5 0.992 0.992 0.976 0.958 0.946 0.932 0.913
0 1.000 1.000 0.983 0.966 0.954 0.939 0.920
Indoor unit is lower
than outdoor unit *2
-5 1.000 1.000 0.983 0.966 0.954 0.939 0.920
-7.5 - 1.000 0.983 0.966 0.954 0.939 0.920
-10 - - 0.983 0.966 0.954 0.939 0.920
-20 - - - 0.966 0.954 0.939 0.920
-30 - - - - 0.954 0.939 0.920
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50
Indoor unit is higher
than outdoor unit *1
30 - - - - 0.934 0.912 0.899
20 - - - 0.957 0.934 0.912 0.899
10 - - 0.969 0.957 0.934 0.912 0.899
7.5 - 1.000 0.969 0.957 0.934 0.912 0.899
5 1.000 1.000 0.969 0.957 0.934 0.912 0.899
0 1.000 1.000 0.969 0.957 0.934 0.912 0.899
Indoor unit is lower
than outdoor unit *2
-5 0.995 0.995 0.964 0.952 0.930 0.907 0.895
-7.5 - 0.993 0.962 0.950 0.927 0.905 0.893
-10 - - 0.959 0.947 0.925 0.903 0.890
-20 - - - 0.938 0.916 0.894 0.881
-30 - - - - 0.906 0.885 0.872