- 113 -
OUTDOOR UNIT
AOYG12-54LB
7. Additional charge calculation
7-1. Model: AOYG12LBLA
Refrigerant charge
7-2. Model: AOYG14LBLA
Refrigerant charge
7-3. Models: AOYG18LBCA and AOYG24LBCA
Refrigerant charge
7-4. Models: AOYG30LBTA and AOYG36LBTA
Refrigerant charge
Refrigerant type R410A
Factory charge amount g 1,150
Total pipe length m 15 or less 20 25 (Max.)
20 g/m
Additional charge amount g 0 100 200
Refrigerant type R410A
Factory charge amount g 1,250
Total pipe length m 15 or less 20 25 (Max.)
20 g/m
Additional charge amount g 0 100 200
Refrigerant type R410A
Factory charge amount g 1,800
Total pipe length m 15 or less 20 30 (Max.)
20 g/m
Additional charge amount g 0 100 300
Refrigerant type R410A
Factory charge amount g 2,100
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge amount g 0 400 800 1200