- 112 -
OUTDOOR UNIT
AOYG12-54LB
6-6. Models: AOYG45LBTA and AOYG54LBTA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50
Indoor unit is higher
than outdoor unit *1
30 - - - - 0.871 0.837 0.803
20 - - - 0.921 0.886 0.851 0.816
10 - - 0.971 0.936 0.901 0.865 0.830
7.5 - 0.988 0.975 0.940 0.904 0.869 0.833
5 0.992 0.992 0.979 0.944 0.908 0.872 0.836
0 1.000 1.000 0.987 0.951 0.915 0.879 0.843
Indoor unit is lower
than outdoor unit *2
-5 1.000 1.000 0.987 0.951 0.915 0.879 0.843
-7.5 - 1.000 0.987 0.951 0.915 0.879 0.843
-10 - - 0.987 0.951 0.915 0.879 0.843
-20 - - - 0.951 0.915 0.879 0.843
-30 - - - - 0.915 0.879 0.843
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50
Indoor unit is higher
than outdoor unit *1
30 - - - - 0.978 0.968 0.958
20 - - - 0.988 0.978 0.968 0.958
10 - - 0.998 0.988 0.978 0.968 0.958
7.5 - 1.000 0.998 0.988 0.978 0.968 0.958
5 1.000 1.000 0.998 0.988 0.978 0.968 0.958
0 1.000 1.000 0.998 0.988 0.978 0.968 0.958
Indoor unit is lower
than outdoor unit *2
-5 0.995 0.995 0.993 0.983 0.973 0.963 0.953
-7.5 - 0.993 0.990 0.980 0.970 0.960 0.950
-10 - - 0.988 0.978 0.968 0.958 0.948
-20 - - - 0.968 0.958 0.948 0.938
-30 - - - - 0.948 0.939 0.929