17) Indoor unit fan control for energy saving for cooling (for Mini duct type only)
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
49
00 Disable
01 Enable
02 Remote controller
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the set-
ting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low
speed.
02: Enable or disable this function by remote controller setting.
NOTES:
As the factory setting, this setting is initially activated.
Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for
energy saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each re-
mote controller.
18) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number Setting value Setting description Factory setting
60
00 Operation status
01—08 (Setting prohibited)
09 Error status
10 Indoor unit fan operation status
11 External heater
DESIGN & TECHNICAL MANUAL
- 248 -
MULTI TYPE
5, 6 ROOMS TYPE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG36LBLA5 and is the answer not in the manual?

Fujitsu AOYG36LBLA5 Specifications

General IconGeneral
TypeAir conditioner outdoor unit
Multi-splitNo
Product colorWhite
Compressor typeRotary
Gas hose diameter9.52 mm
Hose length (max)80 m
Hose length (min)25 m
Inverter technology-
Liquid hose diameter6.35 mm
Refrigerating mediumR410A
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)12500 W
Heating capacity in watts (max)14000 W
Heating capacity in watts (min)3500 W
Cooling capacity in watts (nominal)- W
Operating temperature (cooling) (T-T)-10 - 46 °C
Operating temperature (heating) (T-T)-15 - 24 °C
AC input voltage230 V
AC input frequency50 Hz
Design load (cooling)- kW
Hourly energy consumption (cooling)- kWh
Indoor unit noise level (high speed)- dB
Outdoor unit depth370 mm
Outdoor unit width970 mm
Outdoor unit height998 mm
Outdoor unit weight94000 g
Outdoor units quantity1
Outdoor unit noise level67 dB
Outdoor unit sound power level68 dB