14-2. Test run
CAUTION
Always connect the power supply 12 hours prior to the start of the operation in order to protect
the compressor.
1. Indoor unit
a. Is the drain normal?
b. Is there any abnormal noise and vibration during operation?
2. Outdoor unit
a. Is there any abnormal noise and vibration during operation?
b. Will noise, wind, or drain water from the unit disturb the neighbors?
c. Is there any gas leakage?
Do not operate the air conditioner in the test running state for a long time.
For the operation method of the test run for indoor unit and central remote controller, refer
to the operating manual and perform operation check.
¢
Test run method
Be sure to temporarily disconnect the power supply or turn off the breaker before changing
the DIP switch settings.
1. Check the 3-way valves (both at the liquid side and gas side) are opened. Confirm that
the DIP switch SET1-2 is switched off.
2.
Set the operation mode to “COOL” or “HEAT”. When switching the DIP switch SET1-1
between HEAT and COOL, disconnect the power supply or turn off the circuit breaker be-
forehand.
ON
1 2 3 4
SET1
SET1-1
HEAT
COOL
In the first test run, be sure to set the operation mode to “COOL”.
The operation mode cannot be switched between “COOL” and “HEAT” during the test
run. To switch the operation mode between “COOL” and “HEAT”, stop the test run,
switch the operation mode, and then start the test run again.
3. Press "TEST RUN" switch for more than 3 seconds.
The POWER / MODE LED flashes once.
PUMP DOWN
1WS
TESTRUN
SW1
FEDC
MONITOR
ERROR
BA
POWER
MODE
(1-blink)
4. Confirm operating status.
- 409 -
OUTDOOR UNIT
AOYG45LBLA6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG36LBLA5 and is the answer not in the manual?

Fujitsu AOYG36LBLA5 Specifications

General IconGeneral
TypeAir conditioner outdoor unit
Multi-splitNo
Product colorWhite
Compressor typeRotary
Gas hose diameter9.52 mm
Hose length (max)80 m
Hose length (min)25 m
Inverter technology-
Liquid hose diameter6.35 mm
Refrigerating mediumR410A
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)12500 W
Heating capacity in watts (max)14000 W
Heating capacity in watts (min)3500 W
Cooling capacity in watts (nominal)- W
Operating temperature (cooling) (T-T)-10 - 46 °C
Operating temperature (heating) (T-T)-15 - 24 °C
AC input voltage230 V
AC input frequency50 Hz
Design load (cooling)- kW
Hourly energy consumption (cooling)- kWh
Indoor unit noise level (high speed)- dB
Outdoor unit depth370 mm
Outdoor unit width970 mm
Outdoor unit height998 mm
Outdoor unit weight94000 g
Outdoor units quantity1
Outdoor unit noise level67 dB
Outdoor unit sound power level68 dB