Operating procedure for check run
CAUTION
Initiate check run after more than 12 hours after the power supply is connected.
NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check
run.
1. Press the "CHECK" switch for 3 seconds or more.
2WS
CHECK
2. The number of indoor units (and the places) connected through the communication lines is
displayed.
If the displayed number of units (places) and the installed number of units (places) is the
same, proceed to step 3.
If the displayed number of units (places) and the installed number of units (places) is not
the same, shut off the power and check whether the indoor and outdoor communication
lines are properly connected.
If there is no operation for 1 minute, the LED will return to the original display. (POWER/
MODE LED: ON)
Example: When 4 indoor units (A to D) are connected
FEDC
MONITOR
ERROR
BA
POWER
MODE
(2-blink)
3. Press the "CHECK" switch for 3 seconds or more again. Check run is initiated.
When check run is initiated, all LEDs from A to F will flash. (Preliminary operation)
The LED for each indoor unit will switch off in order as check for each unit is completed.
NOTE:
To interrupt the check run, press the "CHECK" switch.
Example:
When 4 indoor units (A to D) are connected
(2-blink)
FEDC
MONITOR
ERROR
BA
POWER
MODE
DESIGN & TECHNICAL MANUAL
- 330 -
OUTDOOR UNIT
AOYG36LBLA5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG36LBLA5 and is the answer not in the manual?

Fujitsu AOYG36LBLA5 Specifications

General IconGeneral
TypeAir conditioner outdoor unit
Multi-splitNo
Product colorWhite
Compressor typeRotary
Gas hose diameter9.52 mm
Hose length (max)80 m
Hose length (min)25 m
Inverter technology-
Liquid hose diameter6.35 mm
Refrigerating mediumR410A
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)12500 W
Heating capacity in watts (max)14000 W
Heating capacity in watts (min)3500 W
Cooling capacity in watts (nominal)- W
Operating temperature (cooling) (T-T)-10 - 46 °C
Operating temperature (heating) (T-T)-15 - 24 °C
AC input voltage230 V
AC input frequency50 Hz
Design load (cooling)- kW
Hourly energy consumption (cooling)- kWh
Indoor unit noise level (high speed)- dB
Outdoor unit depth370 mm
Outdoor unit width970 mm
Outdoor unit height998 mm
Outdoor unit weight94000 g
Outdoor units quantity1
Outdoor unit noise level67 dB
Outdoor unit sound power level68 dB

Related product manuals