1-10-2. CHECK RUN CHECK ITEMS AND PROCEDURE
Use the following procedure to perform the Check run.
Check Item Procedure When an Error Occurs
1. Turn on
power
1.1 Check
communi-
cations
The power is on to the outdoor unit,
connected branch boxes, and indoor units.
Automatically determined after the power is
turned on.
he determination takes about 2 minutes.
(During this time, the outdoor unit 7 seg.
displays are all lit.)
The determination is pass if all 7 seg. displays
of the outdoor unit turn off.
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
<All lit state> <All off state>
When an error occurred
he number of error is automatically displayed.
he error codes can be checked using the ENTER button.
After checking the error code, turn off the power and resolve the problem.
[Ex] When a branch box error and serial signal error occurred (error during
operation).
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
<Displays the number of error> <Displays error code>
Press ENTER
button
The error code switches each time
the SELECT button is pressed.
1.2 Compressor
preheat
operation
The power is on to the outdoor unit,
connected branch boxes, and indoor units.
After the power is turned on, preheating of the
compressor starts automatically. (Conduct
preheating for at least 12 hours.)
Conf rm that all the outdoor unit 7 seg.
displays are off. (If there is an indoor unit,
branch box, or outdoor unit error, preheating
of the compressor will not be performed.)
[Caution]
If the power has been off for more than 6 hours, preheat the compressor for
at least 12 hours before conducting the Check run.
When an error occurred
he number of error is automatically displayed.
he error codes can be checked using the ENTER button.
After checking the error code, turn off the power and resolve the problem.
urn the power on again.
2. Check run 2.1 Check the
number of
connected
units
Continue pressing the CHECK button for
more than 3 seconds to begin checking the
number of connected units.
After the number of connected units is shown
in the outdoor unit 7 seg. display, check if the
number of installed branch boxes and indoor
units has been detected correctly.
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
<All off state> <Number of units display>
Number of
Branch boxes
Number of
Indoor units
If the number of displayed units does not match the number of
installed units
If the number of units displayed by the outdoor unit indicators does not
match the number of installed branch boxes and indoor units, recheck the
wiring work and perform the Check run again.
2.2 Check
connected
positions
Continue pressing the CHECK button for
more than 3 seconds to begin operation to
check the connected positions.
The determination takes about 1 hour. (During
this time the outdoor unit 7 seg. display will
show "C.rUn".)
The determination is pass when "End" is
displayed on the outdoor unit 7 seg. display.
Ex) mode: HEAT, 6 indoor units
H: HEAT, C: COOL
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
<Check run start>
<Check run
ends normally>
Check run has been completed. Please
conduct the test run.
Wiring Mistake Case 1
Connection destination does not
match
[Display Explanation]
The wire connected to Terminal A
of Branch box1 (left 2-digit) must be
rewired to Terminal B of Branch box
3 (right 2-digit).
[Caution]
The displayed wiring mistake
positions are displayed by the
indicators in order. Make a note of
all of them before turning off the
power and rewiring.
Wiring Mistake Case 2
Problem with the wiring or piping
connection
or
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
[Display Explanation]
Recheck how the wiring and piping
are installed.
(The number of wires and pipes does
not match.)
State in which automatic determination cannot be conducted
LED961 LED962
LED981
POWER
MODE
LED982
ERROR
is displayed
This shows the state in which automatic determination of whether there
are error positions during operation for the 2.2 Check connected positions
cannot be conducted.
In this case, press the MODE/EXIT button to end the Check run.
Since automatic determination is not possible, visually inspect the wiring
and piping and then conduct the test run.
Stopping Check run hen you want to stop Check run before it is completed, press the MODE/EXIT button while “C.rUn” is displayed.
When Check run has been stopped before it is completed, the system is not in a state where it will run normally.
Perform Check run again.

Other manuals for Fujitsu AOYG45LAT8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG45LAT8 and is the answer not in the manual?

Fujitsu AOYG45LAT8 Specifications

General IconGeneral
BrandFujitsu
ModelAOYG45LAT8
CategoryAir Conditioner
LanguageEnglish

Related product manuals