Sub-cool Heat EX. GasInlet Thermistor Error
C
CN65
B
L
A
C
K
B
L
A
C
K
1
2 3 4
1 2 3 4
B
L
A
C
K
B
L
A
C
K
Sub-cooling heat exchanger gas inlet
temperature thermistor
Sub-cooling heat exchanger gas inlet temperature thermistor short or
open detected
1. Connector connection defective, open
2. Thermistor failure3. Main PCB failure
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN65:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Sub-cooling heat exchanger gas inlet thermistor (CN65:1-2)
Indoor Unit : Operation LED 8 times Flash, Timer LED 2 Times Flash,
Economy LED Continuous Flash.
Outdoor Unit : E. 82. 1
Error Code : 82
If the voltage does not appear, replace Main PCB,
and execute the check operation again.
THERMISTOR
(SC.INT.GAS)
THERMISTOR
(SC.OUT.LIQ)
Trouble shooting 23
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
02-39