Trouble shooting 2
INDOOR UNIT Error Method:
Wired Remote Controller
Communication Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash,
Economy LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 1 2
Detective Actuators:
Indoor unit controller PCB
Wired Remote Controller
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor
unit, but the same signal has not been received more than 1 minute.
Check Point 2 : Check Remote controller and Controller PCB
Check terminal voltage of controller PCB Connector. (Power supply for Remote)
If DC12V, Remote Controller failure (Controller PCB is OK) >>> Replace Remote Controller
If DC0V, Controller PCB failure (Remote is OK) >>> Replace Controller PCB and execute the check operation again.
In case of re-installation is done due to removed connector or incorrect wiring, turn on the power again
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote controller and Indoor unit,
and check if there is a disconnection or short of the cable.
OK
DC
Forecast of Cause : 1. Terminal connection abnormal 2. Wired Remote Controller failure 3. Controller PCB failure
Cassette, Duct, Floor / Ceiling Type CN14 ,
Wall mount, Floor Type CN6 ,
Small size Wall mount Type CN305(UTY-XCBXZ14)
02-18

Other manuals for Fujitsu AOYG45LAT8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG45LAT8 and is the answer not in the manual?

Fujitsu AOYG45LAT8 Specifications

General IconGeneral
BrandFujitsu
ModelAOYG45LAT8
CategoryAir Conditioner
LanguageEnglish

Related product manuals