4. CURRENT RELEASE CONTROL
The compressor speed is controlled so that the outdoor unit input current does not exceeds
the current limit value is decided by the outdoor temperature.
When "ECONOMY OPERATION" or "PEAK CUT OPERATION" are effective,
the outdoor unit will operate by lowest current.
( Table 23 : Current release operation value / Release value )
Cooling
Dry
Heating
Outdoor
temperature [ Ta ]
Normal
Low noise
mode 1
Low noise
mode 2
Low noise
mode 3
Current value [ A ]
(Conrtol / Release)
50°C < Ta
47°C < Ta < 50°C
40°C < Ta < 47°C
35°C < Ta < 40°C
30°C < Ta < 35°C
30°C < Ta < 30°C
10°C < Ta < 30°C
-5°C < Ta < 10°C
Ta < -5°C
24°C < Ta
17°C < Ta < 24°C
12°C < Ta < 17°C
5°C < Ta < 12°C
-1°C < Ta < 5°C
-15°C < Ta < -1°C
Ta < -15°C
17.0 / 16.5
18.0 / 17.5
22.0 / 21.5
26.0 / 25.5
22.0 / 21.5
22.0 / 21.5
*20.5 / 20.0
*20.5 / 20.0
*20.5 / 20.0
19.0 / 18.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
14.0 / 13.5
16.5 / 16.0
17.0 / 16.5
22.0 / 21.5
22.0 / 21.5
22.0 / 21.5
*20.5 / 20.0
*20.5 / 20.0
*20.5 / 20.0
19.0 / 18.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
13.0 / 12.5
15.0 / 14.5
15.5 / 15.0
17.0 / 16.5
17.0 / 16.5
19.0 / 18.5
*20.5 / 20.0
*20.5 / 20.0
*20.5 / 20.0
19.0 / 18.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
26.0 / 25.5
10.5 / 10.0
12.5 / 12.0
13.0 / 12.5
14.0 / 13.5
14.0 / 13.5
16.0 / 15.5
*20.5 / 20.0
*20.5 / 20.0
*20.5 / 20.0
19.0 / 18.5
23.5 / 23.0
23.5 / 23.0
23.5 / 23.0
23.5 / 23.0
23.5 / 23.0
23.5 / 23.0
*Current value(Control / Release) is different from the operating fan step of the outdoor unit.
(Above case is more than 4 STEP, refer to outdoor unit fan table.)
Cooling
Dry
STEP 0, 1 : 11.0 / 10.5
STEP 3 : 16.5 / 16.0
STEP 2 : 13.5 / 13.0
10°C < Ta < 30°C
-5°C < Ta < 10°C
< Ta < -5°C
When the outdoor unit input current reaches to the control value, the compressor speed
-1rps every 1 second till the release value.
Then, if the compressor operates at minimum speed and the input current doesn't reach
to the release value, the compressor is stopped.
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Ta : Outdoor temperature
01-43