- (01 - 16) -
DUCT TYPE
ARTG54LHTC
DUCT TYPE
ARTG54LHTC
FAN PERFORMANCE AND CAPACITY7.
MODEL
: ARTG54LH
Q-h Characteristic curve
Hi(SP mode3)
Hi
(Normal SP mode)
Med(Normal SP mode)
Normal SP mode Lower limit
Lo(Normal SP mode)
Normal SP mode
Upper limit
Hi(SP mode2)
Hi(SP mode1)
Hi(SP mode4)
300
250
200
150
100
50
0
Static pressure(Pa)
Air ow
1,000 1,500 2,000 2,500 3,000 3,500 4,000 (m
3
/h)
278 417 556 695 833 972 1,111 (l/s)
Cooling
z
Q-q Performance curve
92
94
96
98
100
102
2,300 2,500 2,700 2,900 3,100 3,300 3,500 3,700(m
3
/h)
639 695 750 806 861 917 972 1,028(l/s)
Air flow
Capacity(%)
Capacity
Heating
z
Q-q Performance curve
92
94
96
98
100
102
Air flow
Capacity(%)
2,300 2,500 2,700 2,900 3,100 3,300 3,500 3,700(m
3
/h)
639 695 750 806 861 917 972 1,028(l/s)
Capacity