EasyManua.ls Logo

Fujitsu ARTG54LHTC - Low Noise Mode; Setting Method

Fujitsu ARTG54LHTC
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- (02 - 22) -
OUTDOOR UNIT
AOTG54LCTL
OUTDOOR UNIT
AOTG54LCTL
SETTING METHOD15-2.
• Stop the operation of air conditioner before this setting.
LOW NOISE MODE15-2-1.
SW1
SW2
SW3 SW4 SW5
LED lamp part
(1) Switch to “Local setting mode” by pressing [MODE] button (SW1) for 3 seconds or more.
(2) Conrm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW3).
POWER
MODE
ERROR
(L1) (L2) (L3) (L4) (L5) (L6)
PUMP
DOWN
LOW NOISE PEAK CUT
Blinks
(9 times)
Sign “ ” : Lights off
(3) Press [SELECT] button (SW2), and adjust LED lamp as shown below. (Current setting is
displayed)
(L2)
(L3)
LOW NOISE
Blink
LOW NOISE
MODE
(4) Press [ENTER] button (SW3).
(L2) (L3)
LOW NOISE
LOW NOISE
MODE
Sign “ ” : Lights on
(5) Press [SELECT] button (SW2), and adjust LED lamp as shown in below gure.
PEAK CUT
MODE 1
MODE 2
Blink
Blink
(L4) (L5) (L6)
(6) Press [ENTER] button (SW3) and x it.
PEAK CUT
MODE 1
MODE 2
(L4) (L5) (L6)
(7) Return to “Operating status display (Normal operation)” by pressing [EXIT] button (SW4).
• In case of missing how many times [SELECT] and [ENTER] button are pressed, restart from the beginning of
operation procedure after returning to “Operation status display (normal operation)” by pressing the [EXIT] button
once.