- (01 - 35) -
DUCT TYPE
ARTG54LHTC
DUCT TYPE
ARTG54LHTC
WIRED REMOTE CONTROLLER12-3.
AR-WDD1E (Option: UTY-RVNYN)12-3-1.
DIP
Switch
SW1
Memory backup setting
SW2
Dual remote controller setting
Switch position
z
DIP Switch setting
z
Memory backup setting
●
Set to ON to use batteries for the memory backup.
If batteries are not used, all of settings stored in memory will be deleted if there is a power
failure.
(
...Factory setting)
SW1 Memory backup
OFF Invalidity
ON Validity
Dual remote controller setting
●
Set the remote controller SW2 according to the following table.
(
...Factory setting)
Number
of remote
controller
Primary unit
Secondary
unit
SW2 SW2
1 (Normal) OFF -
2 (Dual) OFF ON
Indoor unit
Remote controller cable
Primary unit
Secondary
unit
Remote controller
Junction box
(eld supply)