DUCT TYPE
ARTG54LHTC
DUCT TYPE
ARTG54LHTC
6. Room temperature sensor switching function
• (Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
(
. . .Factory setting)
Setting description Function number Setting value
Indoor unit
42
00
Both 01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
*Remote controller sensor must be turned on by using the remote controller.
7. Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When disabled, the fan setting will always follow the
setting on the remote controller. (Excluding defrost mode)
(
. . .Factory setting)
Setting description Function number Setting value
Enable
43
00
Disable 01
8. External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
. . .Factory setting)
Setting description Function number Setting value
Operation/Stop mode
46
00
(Setting prohibited) 01
Forced stop mode 02
9. Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
(
. . .Factory setting)
Setting description Function number Setting value
Both
48
00
Wired remote controller 01