- (01 - 33) -
DUCT TYPE
ARTG54LHTC
DUCT TYPE
ARTG54LHTC
CONTENTS FUNCTION SETTING12-2-3.
1. Filter sign
• Select appropriate intervals for displaying the lter sign on the indoor unit according to the estimated amount of dust in the air of the
room.
If the indication is not required, select "No indication" (03).
(
. . .Factory setting)
Setting description Function number Setting value
Standard (2500 hours)
11
00
Long interval (5000 hours) 01
Short interval (1250 hours) 02
No indication 03
2. Static pressure
• Select the appropriate static pressure according to the installation conditions.
(
. . .Factory setting)
Setting description Function number Setting value
Normal (60Pa)
21
00
Static pressure 1 (100Pa) 02
Static pressure 2 (150Pa) 03
Static pressure 3 (200Pa) 04
Static pressure 4 (250Pa) 05
3. Room temperature control for cooling
• Depending on the installed environment, correction of the room temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
(
. . .Factory setting)
Setting description Function number Setting value
Standard
30
00
Higher control 01
Slightly higher control 02
Slightly lower control 03
Lower control 04
4. Room temperature control for heating
• Depending on the installed environment, correction of the room temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
(
. . .Factory setting)
Setting description Function number Setting value
Standard
31
00
Higher control 01
Slightly higher control 02
Slightly lower control 03
Lower control 04
5. Auto restart
• Enable or disable automatic restart after a power interruption.
(
. . .Factory setting)
Setting description Function number Setting value
Enable
40
00
Disable 01
• Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.