EasyManua.ls Logo

Fujitsu ARTG54LHTC - External Input; External Input & Output

Fujitsu ARTG54LHTC
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- (02 - 17) -
OUTDOOR UNIT
AOTG54LCTL
OUTDOOR UNIT
AOTG54LCTL
EXTERNAL INPUT & OUTPUT14.
EXTERNAL INPUT14-1.
ON/OFF of the "Low noise mode" and "Peak cut mode" functions can be specied by external
signal.
LOW NOISE MODE
The following reduces the operating sound of the outdoor unit from the normal sound.
The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial
timer or ON/OFF switch to a connector on the outdoor control PC board.
* Performance may drop depending on the outside air temperature condition, etc.
Circuit diagram example
z
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*10m
Connected unit
Ex.) Switch
Contact capacity : 24VDC or more, 10mA or more.
* Make the distance from the PC board to the connected unit within 10m.
Use the following parts and construct a circuit as shown above.
Input Signal∙ON : Low noise mode, Input Signal∙OFF : Normal operation
* Set the "Low noise mode" type by "Push switch" on the outdoor control PC board.
ON
OFF
ON
OFF
Input Signal
Low noise mode
Parts (Optional)
z
Parts name External connect kit
Model name UT Y-XWZ XZ3
Input Output Connector Remarks
Low noise mode CN10
See external
input/output settings
for details.
Peak cut mode CN11
Error status CN12
Compressor status CN13

Other manuals for Fujitsu ARTG54LHTC

Related product manuals