- (01 - 29) -
DUCT TYPE
ARTG54LHTC
DUCT TYPE
ARTG54LHTC
DIP-SW SETTING
Remote controller address setting (SW50)
z
A number of indoor units can be operated at the same time using a single remote controller.
Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board.
(See the following table.)
The DIP switches are normally set to make the unit number 00.
(
. . .Factory setting)
Remote controller address
DIP switch No.
1 2 3 4
00 OFF OFF OFF OFF
01 ON OFF OFF OFF
02 OFF ON OFF OFF
03 ON ON OFF OFF
04 OFF OFF ON OFF
05 ON OFF ON OFF
06 OFF ON ON OFF
07 ON ON ON OFF
08 OFF OFF OFF ON
09 ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON
JUMPER WIRE SETTING
JM40, 41 setting prohibited
z
Fan delay setting (JM42)
z
When the indoor unit is stopped while operating in conjunction with auxiliary heater, the indoor unit
fan operation will continue for one minute.
(
. . .Factory setting)
JM 3 / JM 42 JM state
Connect Invalid
Disconnect Valid