(3).COOLING OPERATION
Switch the airflow [AUTO], and the (Fig.6)
indoor fan motor will run according airflow change - over ( Cooling:AUTO )
to a room temperature, as shown in When the room
Figure 6. temperature rises
On the other hand, if switched in HIGH mode
[HIGH] [QUIET], the indoor motor +2.5
will run at a constant airflow of [COOL] +2.0
operation modes QUIET, LOW, MED, MED mode
HIGH, as shown in Table 5. +1.5
+1.0
LOW mode
When the room
temperature lowers
(Room temperature) D (Setting temperature)
(4).DRY OPERATION
(5).HEATING OPERATION
Switch the airflow [AUTO], and the (Fig.7)
indoor fan motor will run according airflow change - over ( Heating:AUTO)
to a room temperature, as shown in When the room
Figure 7. temperature rises
On the other hand, if switched
LOW mode
[HIGH] [QUIET], the indoor motor -1.0
will run at a constant airflow of [HEAT] -1.5
operation modes QUIET, LOW, MED, MED mode
HIGH, as shown in Table 5. -2.0
-2.5
MED + mode
When the room
temperature lowers
(Room temperature) D (Setting temperature)
(6).COOL AIR PREVENTION CONTROL (Heating mode)
Indoor heat exchanger Indoor heat exchanger
temperature temperature
47 Hi
40 Me+ 40
37
Lo 34
Cool air prevention 32
30
28
S-Lo
Refer to the table 4.
Durring the dry mode operation, the fan speed
setting can not be changed.
The maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.8 : Cool Air Prevention Control)
05-06