20. VARIOUS PROTECTIONS
(1). DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
AS*9LSACW 104 C 101 C 110 C
AS*12LSACW 104 C 101 C 110 C
AS*9LSBCW 104 C 101 C 110 C
AS*12LSBCW 104 C 101 C 110 C
AS*14LSBCW 104 C 101 C 110 C
AS*18LSBCW 104 C 101 C 110 C
AS*9LSACW AS*12LSACW AS*9LSBC W AS*12LSBCW AS*14LSBCW AS*18LSBCW
OT (Control / Release)
6.5A / 6.0A
17 C
8.0A / 7.5A
12 C
8.0A / 7.5A
8.0A / 7.5A
6.5A / 6.0A
8.0A / 7.5A
8.5A / 8.0A
9.5A / 9.0A
6.5A / 6.0A
8.0A / 7.5A
8.0A / 7.5A
8.0A / 7.5A
6.5A / 6.0A
8.0A / 7.5A
8.5A / 8.0A
9.5A / 9.0A
7.0A / 6.5A
9.0A / 8.5A
10.5A / 10.0A
12.0A / 11.5A
7.0A / 6.5A
9.0A / 8.5A
10.5A / 10.0A
12.0A / 11.5A
AS*9LSACW AS*12LSACW AS*9LSBCW AS*12LSBCW AS*14LSBCW AS*18LSBCW
3.5A / 3.0A
46 C
4.0A / 3.5A
40 C
5.5A / 5.0A
4.0A / 3.5A
5.0A / 4.5A
6.5A / 6.0A
3.5A / 3.0A
4.0A / 3.5A
5.5A / 5.0A
4.0A / 3.5A
5.0A / 4.5A
6.5A / 6.0A
4.5A / 4.0A
6.0A / 5.5A
8.5A / 8.0A
4.5A / 4.0A
6.0A / 5.5A
8.5A / 8.0A
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the
compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table 17 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
(2). CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 18 : Current Release Operation Value / Release Value)
[ Heating ]
[ Cooling / Dry ]
OT : Outdoor Temperature
OT (Control / Release) OT (Control / Release)
OT (Control / Release)
OT (Control / Release)
OT (Control / Release)
OT : Outdoor Temperature
OT (Control / Release) OT (Control / Release)
OT (Control / Release)
OT (Control / Release) OT (Control / Release)
OT (Control / Release)
5 C
17 C
12 C
5 C
17 C
12 C
5 C
17 C
12 C
5 C
17 C
12 C
5 C
17 C
12 C
5 C
46 C
40 C
46 C
40 C
46 C
40 C
46 C
40 C
46 C
40 C