- 8 -
WALL MOUNTED
ASTG30, 34KMTA
3. Specifications
Type
Wall mounted
Inverter heat pump
Model name
ASTG30KMTA ASTG34KMTA
Power supply 240 V ~ 50 Hz
Available voltage range 198—264 V
Star rating index 10-star standard
Cooling 2.0 2.0
Heating 3.0 2.5
Capacity
Cooling
Rated
kW 8.50 9.40
Btu/h 29,000 32,000
Min.—Max.
kW 2.9—10.5 2.9—11.2
Btu/h 9,900—35,800 9,900—38,200
Heating
Rated
kW 9.00 10.30
Btu/h 30,700 35,100
Min.—Max.
kW 2.2—11.2 2.7—11.7
Btu/h 7,500—38,200 9,200—39,900
Input power
Cooling
Rated
kW
2.46 2.78
Min.—Max. 0.58—3.85 0.59—4.03
Heating
Rated 2.34 2.84
Min.—Max. 0.50—4.01 0.60—4.24
Fan W 63 63
Current
Cooling
Rated A
10.4 11.7
Heating 10.1 12.9
EER Cooling
kW/kW
3.45 3.38
COP Heating 3.84 3.63
Sensible capacity Cooling kW 6.00 6.95
Power factor
Cooling
%
98.5 99
Heating 97 99
Moisture removal L/h (pints/h) 2.5 (4.4) 3.5 (6.16)
Maximum operating current *1
Cooling
A
17.0 19.5
Heating 17.0 20.5
Fan
Airflow rate
Cooling
HIGH
l/s (m
3
/h)
389 (1,400)
MED 319 (1,150)
LOW 256 (920)
QUIET 200 (720)
Heating
HIGH 389 (1,400)
MED 319 (1,150)
LOW 256 (920)
QUIET 200 (720)
Type × Q'ty Cross flow fan × 1
Motor output W 80
Sound pressure level *2
Cooling
HIGH
dB(A)
51 52
MED 46 47
LOW 40 41
QUIET 33 34
Heating
HIGH 51 51
MED 44 44
LOW 39 38
QUIET 33 33
Heat exchanger type
Dimensions (H × W × D)
mm
Main: 448 × 900 × 30
Sub1: 126 × 900 × 13.3
Sub2: 84 × 900 × 13.3
Fin pitch Main: 1.2, Sub: 1.4
Rows × Stages Main: 3 × 28, Sub1: 1 × 6, Sub2: 1 × 4
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Polystyrene
Color
White
Approximate color of Munsell N 9.25/
Dimensions
(H × W × D)
Net
mm
340 × 1,150 × 280
Gross 450 × 1,270 × 405
Weight
Net
kg
18
Gross 24
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Drain hose
Material PVC
Size mm Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller type Wireless (Wired [option])
International Protection rating IPX0
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: Maximum current is maximum value when operated within the operation range.
*2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.