En-7
7.2.
Indoor unit wiring
(1) Remove the intake grill. (Refer to “9.1. Intake grill removal and installation”.)
(2) Remove the tapping screw for the wire cover and remove the wire cover.
Screw
Wire cover
(3) Remove the tapping screw and while minding the cable clamp hook, remove the cable
clamp.
Screw
Cable clamp
Hook
7.3. How to connect wiring to the terminals
Caution when wiring cable
To strip off the insulation of a lead wire, always use a special tool such as a wire stripper.
If there is no special tool, carefully strip off the insulation by using a knife or other utensil.
(1) Use ring terminals with insulating sleeves as shown in the gure to connect to the
terminal block.
(2) Securely clamp the ring terminals to the wires by using an appropriate tool so that the
wires do not come loose.
Strip : 10 mm
Ring terminal
Sleeve
(3) Connect speci ed wires securely, and fasten them so that there is no stress applied on
the terminals.
(4) Use a screwdriver with an appropriate bit size to tighten the terminal screws. Using of
screwdriver with inappropriate bit size will damage the screw heads, and the screws
will not be tightened properly.
(5) Do not overtighten the terminal screws. Otherwise, the screws may break.
Screw with special washer
Wire
Ring terminal
Terminal blocks
Wire
Screw with special washer
Ring terminal
(6) See the table for the terminal screw tightening torques.
Tightening torque [N·m (kgf·cm)]
M4 screw 1.2 to 1.8 (12 to 18)
CAUTION
Match the terminal block numbers and connection cable colors with those of the
outdoor unit. Incorrect wiring may cause a re.
Connect the connection cables rmly to the terminal block. Imperfect installation may
cause a re.
When xing the connection cable with the cable clamp, always fasten the cable at the
plastic jacket portion, but not at the insulator portion. If the insulator is chafed, electric
leakage may occur.
Always connect the earth (ground) wire. Improper earthing (grounding) work can
cause electric shocks.
Do not use the earth (ground) screw for the indoor unit to the outdoor unit unless it is
speci ed.
6.6.3. Pipe connection
WARNING
The are connection shall not be performed indoors.
CAUTION
Be sure to Install the pipe against the port on the indoor unit correctly. If the centering
is improper, the are nut cannot tighten smoothly. If the are nut is forced to turn, the
threads will be damaged.
Do not remove the are nut from the indoor unit pipe until immediately before con-
necting the connection pipe.
Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order
to tighten the are nut correctly.
Tighten the are nuts with a torque wrench using the speci ed tightening method.
Otherwise, the are nuts could break after a prolonged period, causing refrigerant to
leak and generate hazardous gas if the refrigerant comes into contact with a ame.
Connect the piping so that the control box cover can easily be removed for servicing
when necessary.
In order to prevent water from leaking into the control box, make sure that the piping
is well insulated.
When the flare nut is tightened properly by your hand, hold the body side coupling with a
wrench, then tighten with a torque wrench. (See the table below for the flare nut tightening
torques.)
Tighten with 2 wrenches.
Holding wrench
Flare nut
Connection pipe
Torque wrench
Indoor unit pipe
(Body side)
Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
Do not remove the cap from the connection pipe before connecting the pipe.
7. ELECTRICAL WIRING
CAUTION
Be careful not to generate a spark as follows for using a ammable refrigerant.
Do not remove the fuse while the power is on.
Do not disconnect the wiring while the power is on.
It is recommended to position the outlet connection in a high position. Place the
cords so that they do not get tangled.
7.1.
Wiring system diagram
WARNING
Before connecting the wires, make sure the power supply is OFF.
Every wire must be connected rmly.
No wire should be allowed to touch refrigerant tubing, the compressor, or any mov-
ing part.
Loose wiring may cause the terminal to overheat or result in unit malfunction. A re
hazard may also exist. Therefore, be sure all wiring is tightly connected.
Connect wires to the matching numbers of terminals.
Earth (Ground) line
OUTDOOR UNIT
Please connect to the
speci ed terminal.
INDOOR UNIT
TERMINAL
Power line
Control line
9319357096_IM.indb 79319357096_IM.indb 7 2016/8/31 13:33:152016/8/31 13:33:15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG09KXCA series and is the answer not in the manual?

Fujitsu ASYG09KXCA series Specifications

General IconGeneral
BrandFujitsu
ModelASYG09KXCA series
CategoryAir Conditioner
LanguageEnglish

Related product manuals