6. SYSTEM DESIGN
RESTRICTIONS APPLICABLE WHEN PERFORMING THE CHECK 
RUN
When the Check run starts, all indoor units connected to the outdoor unit will start to run 
automatically. During the Check run, you cannot check the operation of the indoor units 
separately. After the Check run, check the operation of the indoor units separately in normal 
operation.
The operable temperature ranges for the Check run are: outdoor temperature -15 to 46ºC; indoor 
temperature for cooling 18 to 46ºC; indoor temperature for heating -15 to 37ºC.
In the check run, the conditioner will automatically switch between cooling and heating 
depending on the outdoor temperature and indoor temperature. If the outdoor temperature or 
indoor temperature is outside the above operable temperature range, wait until the temperature 
is within the operable range and then perform the Check run.
Please do not conduct the Check run with all the windows in the room closed. Otherwise the 
indoor temperature could get too low or too high.
Depending on the difference of the indoor temperature of each room, a judgment may be 
impossible.