6. SYSTEM DESIGN
EXAMPLE3
When connection destination does not match.
INDOOR UNIT A      INDOOR UNIT B      INDOOR UNIT C  INDOOR UNIT A      INDOOR UNIT B      INDOOR UNIT C  INDOOR UNIT A      INDOOR UNIT B 
Indoor 
unit 1
Indoor 
unit 2
Indoor 
unit 3
Indoor 
unit 4
Indoor 
unit 5
Indoor 
unit 6
Indoor 
unit 7
Branch box 1 (Primary) Branch box 2 (Secondary) Branch box 3 (Secondary)
[Display (Check run ends)]
Branch box 1
Indoor unit A
Branch box 3
Indoor unit B
to
 LED961 LED962
LED981
POWER
MODE
LED982
ERROR
[Coping process]
The wire connected to Terminal Indoor unit A of Branch box1(Primary) must be rewired to 
Terminal Indoor unit B of Branch box 3(Secondary).
[After correcting wiring]
INDOOR UNIT A      INDOOR UNIT B      INDOOR UNIT C  INDOOR UNIT A      INDOOR UNIT B      INDOOR UNIT C  INDOOR UNIT A      INDOOR UNIT B 
Indoor 
unit 1
Indoor 
unit 2
Indoor 
unit 3
Indoor 
unit 4
Indoor 
unit 5
Indoor 
unit 6
Indoor 
unit 7
Branch box 1 (Primary) Branch box 2 (Secondary) Branch box 3 (Secondary)
- (06 - 100) -
SYSTEM
DESIGN
SYSTEM
DESIGN