01 - 37
-
CASSETTE TYPE
AU
G12-24LVL
CASSETTE TYPE
AU
G12-24LVL
FRESH AIR CONTROL OUTPUT
A signal linked to air conditioner indoor fan ON can be output.
* However, signal becomes OFF during cold air prevention control operation.
Circuit diagram example
Field supply
Indoor
control PC board
Connector
1
12 V
on/off
2
Signal
Relay
power
supply
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Rated 12VDC, 50mA or less.
Ex.) Fan
Connected unit
Ex.) Relay unit
*10 m
ON
OFF
Operation
Stop
Indoor fan
Output signal
Parts (Optional)
Model name
UTZ-VXAA *1
Wire (Fresh air output)
Note This wire is included in Fresh air intake kit (UTZ-VXAA)