02 - 06
-
OUTDOOR UNIT
AO
G12-24LAL
OUTDOOR UNIT
AO
G12-24LAL
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 5.
AND HEIGHT DIFFERENCE
This table is created using the maximum capacity.
MODEL
:AO
G12LALL
HEATING
Pipe length (m)
57.510152025
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15 - - - 0.943 0.916 0.896
10 - - 1.010 0.943 0.916 0.896
7.5 - 1.000 1.010 0.943 0.916 0.896
5 1.000 1.000 1.010 0.943 0.916 0.896
0 1.000 1.000 1.010 0.943 0.916 0.896
2
Indoor unit is
lower than
outdoor unit.
-5 0.995 0.995 1.005 0.939 0.912 0.892
-7.5 - 0.993 1.002 0.936 0.909 0.890
-10 - - 0.999 0.934 0.907 0.887
-15 - - - 0.925 0.898 0.878
COOLING
Pipe length (m)
57.510152025
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15 - - - 0.903 0.894 0.867
10 - - 0.964 0.918 0.909 0.881
7.5 - 0.988 0.968 0.922 0.912 0.885
5 0.992 0.992 0.972 0.925 0.916 0.888
0 1.000 1.000 0.980 0.933 0.923 0.895
2
Indoor unit is
lower than
outdoor unit.
-5 1.000 1.000 0.980 0.933 0.923 0.895
-7.5 - 1.000 0.980 0.933 0.923 0.895
-10 - - 0.980 0.933 0.923 0.895
-15 - - - 0.933 0.923 0.895
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH