02 - 01
-
OUTDOOR UNIT
AO
G12-24LAL
OUTDOOR UNIT
AO
G12-24LAL
SPECIFICATIONS1.
Type INVERTER HEAT PUMP
Model name AO
G12LALL AO
G14LALL AO
G18LALL AO
G24LALA
Power source 230V ~ 50Hz
Available voltage range 198 - 264V ~ 50Hz
Starting current A 5.1 6.1 7.4 9.9
Fan
Airflow rate
Cooling
m
3
/h
1780 1910 2000 2470
Heating 1630 1740 1910 2470
Type × Q'ty Propeller × 1
Motor output W 54 65
Sound pressure level
Cooling
dB (A)
47 49 50 52
Heating 48 49 50 53
Sound power level
Cooling
dB (A)
61 62 62 67
Heating 63646570
Heat exchanger type
Dimensions
(H × W × D)
mm
546 × 876 × 18.2
546 × 842 × 18.2
546 × 866 × 18.2
546 × 832 × 18.2
504 × 589 × 18.2
Fin pitch 1.30 1.40
Rows × Stages 2 × 26
2 × 26
1 × 24
Pipe type Copper
Fin Type Aluminium
Compressor
Type × Q'ty Twin Rotary × 1
Motor output W 1100
Refrigerant
Type
(Global Warming Potential)
R410A(1975)
Charge g 1150 1250 1700
Refrigerant oil Type POE
Enclosure
Material Steel sheet
Colour
Beige
Approximate colour of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
mm
578 × 790 ×300 578 × 790 ×315
Gross 648 × 910 × 380
Weight
Net
kg
40 44
Gross 44 48
Connenction pipe
Size
Liquid
mm
Ø6.35 (Ø1/4 in.)
Gas Ø9.52 (Ø3/8 in.) Ø12.70 (Ø1/2 in.) Ø15.88 (Ø5/8 in.)
Method Flare
Pre-charge length
m
15
Max. length 25 30
Max. height difference 15 20
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB / 24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB / 6 °CWB.
Pipe length : 5.0 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
The protective function may work when using it outside the operation range.