SPECIFICATIONS3.
Type
CASSETTE MODEL
INVERTER HEATPUMP
Model name
Indoor unit AU
G12LVLB AU
G14LVLB AU
G18LVLB AU
G24LVLA
Outdoor unit AO
G12LALL AO
G14LALL AO
G18LALL AO
G24LALA
Power source 230V ~ 50Hz
Available voltage range 198-264V ~ 50Hz
Capacity
Cooling
Rated
kW 3.50 4.30 5.20 6.80
Btu/h 11950 14650 17700 23200
Min. - Max.
kW 0.90 - 4.40 0.90 - 5.40 0.90 - 5.90 0.90 - 8.00
Btu/h 3100 - 15000 3100 - 18400 3100 - 20100 3100 - 27300
Heating
Rated
kW 4.10 5.00 6.00 8.00
Btu/h 14000 17050 20500 27300
Min. - Max.
kW 0.90 - 5.70 0.90 - 6.50 0.90 - 7.50 0.90 - 9.10
Btu/h 3100 - 19400 3100 - 22100 3100 - 25600 3100 - 31000
Input power
Cooling
Rated
kW
1.05 1.33 1.62 2.21
*Max. 1.70 2.04 2.04 2.85
Heating
Rated 1.11 1.34 1.66 2.26
*Max. 2.26 2.83 2.83 3.19
Current
Cooling
Rated A
4.8 6.1 7.2 9.7
Heating 5.1 6.1 7.4 9.9
EER Cooling
kW / kW
3.33 3.21 3.21 3.08
COP Heating 3.69 3.71 3.61 3.54
Moisture removal l/h (pints/h) 1.2 ( 2.1 ) 1.5 ( 2.6 ) 2.2 ( 3.9 ) 2.7 ( 4.8 )
Maximum operating current *1
Cooling
A
7.5 9.0 9 .0 12.0
Heating 10.0 12.5 12.5 13.5
Fan
Airflow
rate
Cooling
High
m
3
/h
600 680 680 930
Med 530 580 580 830
Low 470 490 490 600
Quiet 410 410 410 450
Heating
High 600 800 800 930
Med 530 680 680 860
Low 470 580 580 700
Quiet 410 450 450 530
Type × Q'ty Turbo × 1
Motor output W 54
Sound pressure level
Cooling
High
dB (A)
37 38 38 49
Med 34343444
Low 30303036
Quiet 27 27 26 30
Heating
High 37 43 43 49
Med 34 38 38 45
Low 31 34 34 40
Quiet 29 30 30 33
Heat exchanger type
Dimensions
(H × W × D)
mm
210 × 1310 × 13.3
210 × 1250 × 13.3
210 × 1375 × 13.3
210 × 1310 × 13.3
210 × 1250 × 13.3
Fin pitch 1.20 1.45
Rows × Stages 2 × 10 3 × 10
Pipe type Copper tube
Fin type Aluminium
Dimensions
(H × W × D)
Net
mm
245 × 570 × 570
Gross 265 × 730 × 625
Weight
Net
kg
15 16
Gross 18 19
Connection pipe
Size
Liquid
mm
Ø 6.35 (Ø 1 / 4 in.)
Gas Ø9.52 (Ø3/8 in.) Ø12.70 (Ø1/2 in.) Ø15.88 (Ø5/8 in.)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Cassette grille
Model name UTG-UF
D-W
Material PS
Colour
WHITE
Approximate colour of MUNSELL N 9.25 /
Dimensions
(H × W × D)
Net
mm
49 × 700 × 700
Gross 120 × 765 × 755
Weight
Net
kg
2.6
Gross 4.5
Remote controller type Wireless [Wired (option)]
Drain hose
Material PVC
Size mm VP25 [Ø25(I.D.),Ø32(O.D.)]
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB. and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / 15°CWB. and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 5.0 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
Ceiling mode : Standard
*The maximum current and the maximum input value are the maximum value when operated within the operation range.
The protective function might work when using outside the operation range.